| Phase | 1 Phase In / 1 Phase Out |
|---|
| Capacity | 6000 VA / 6000 W |
|---|
| INPUT |
| Nominal Voltage | 208 / 220 / 230 / 240VAC |
|---|
| Voltage Range | 110-300 VAC ± 3% at 50% Load 176-300 VAC ± 3% at 100% Load |
|---|
| Frequency Range | 46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz 40 Hz ~ 70 Hz (In generator mode) |
|---|
| Power factor | ≥ 0.99 @ Full load |
|---|
| OUTPUT |
| Output Voltage | 208 / 220 / 230 / 240 VAC |
|---|
| AC Voltage Regulation (Batt. Mode) | ± 1 % |
|---|
| Frequency Range (Synchronized Range) | 46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz |
|---|
| Frequency Range (Battery Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 % |
|---|
| Current Crest Ratio | 3:1 |
|---|
| Harmonic Distortion | ≤ 1%THD (Linear Load) ; ≤ 4%THD (Non-linear Load) |
|---|
| TOPOLOGY |
| Transfer Time AC Mode to Batt. Mode | Zero |
|---|
| Transfer Time Inverter to Bypass | Zero |
|---|
| Waveform (Batt. Mode) | Pure Sinewave |
|---|
| EFFICIENCY |
| AC Mode | 94% |
|---|
| Battery Mode | 92% |
|---|
| BATTERIES |
| Battery Capacity | 12V / 7AH |
|---|
| Number of Batteries (WPS Model) | 16 - 20 (configurable) |
|---|
| Typical Recharge Time | 9 hours recover to 90% capacity |
|---|
| Charging Current (Max.) | 1A (default) |
|---|
| COMMUNICATIONS / MANAGEMENT |
| Smart RS232 / USB | Supports Windows® 2000 / 2003 / XP / Vista / 2008 , Windows® 7 / 8, Linux, Unix and MAC |
|---|
| Intelligent Slot | SNMP / AS400 Card |
|---|
| STANDARDS / APPROVALS |
| Compliances | CE |
|---|
| IP Rating | IP 20 |
|---|
| ENVIRONMENT |
Operating Temperature | 0°C ~ 40°C |
|---|
| Relative Humidity | 20-95 % (non-condensing) |
|---|
| Acoustic Level at 1m | ≤ 55dB @ 1Meter |
|---|
| PHYSICAL PROPERTIES |
| Dimensions (W x D x H) mm | 438 x 515 x 88 |
|---|
| Net weight (kg) | 11.0 |
|---|
| WARRANTY & SUPPORT |
| Product Warranty | 3 Years Warranty on UPS Parts and Labour. 2 Years on Warranty on VRLA Rechargeable Batteries. |
|---|